          | Specification |  |  
          | Rated Voltage | 415V, 3PH. Wire,50 / 60 Hz |  
          | Rated Current | 3A, 6A ,15A & 30A |  
          | Test Voltage | 1500v ac between Main terminals Shorted together & earth for 60 Secs. |  
          | Insulation Resistance | > 100 m ohm between mains terminals shorted together & earth at 500 V DC |  
          | Leakage Current | 2  mA max at 415 V, 50Hz |  
          | Voltage Drop | 1 V rms Max |  
          | Operating Temperature Range | 0 to 85 Celsius 
 |  
          | Surge Suppressor | Clamping Voltage 715 V Response Time 100n Sec. |  
          | Insertion Loss |  
          | Current Ratings AMPS |  | 3 | 6 | 15 | 30 |  |  
          | Common Mode Insertion Loss (dB in a 50 ohm system)
 FREQUENCY-MHz
 | 0.15 | >25 | >15 | >8 | >5 |  |  
          | 0.5 | >30 | >20 | >12 | >10 |  |  
          | 1.0 | >35 | >30 | >20 | >18 |  |  
          | 5.0 | >40 | >35 | >30 | >28 |  |  
          | 10 | >45 | >40 | >35 | >40 |  |  
          | 30 | >50 | >45 | >40 | >35 |  |  
          | Mechanical Diagram | All Dimensions In MM |  
          |  |  | 
  
  
    |  |  |  |  | 
  
    |  |  | RF I/ EMI Filters For AC Drives ( Input Filter Sak-Drv & Output Filter Sak-Dro) | 
  
    |  |  | 
  
    |  | 
      
        
          | Specification |  |  
          | Voltage | 440Vac, 50Hz,3 wire System |  
          | Leakage Current | 3mA@440V ac, 13mA@2500V ac for 1 minute |  
          | Insulation | 500 V DC, 500M ohm, (Line to earth for 1 Sec) |  
          | Resistance | > 100 m ohm between mains terminals shorted together & earth for 60 Sec's |  
          | Break down Voltage | 2500V ac -Line to earth for 1 min. |  
          | Overload Capacity | 150 % for 1 min Max |  
          | Humidity | 95% |  
          | Temp | 55 C |  
          | Attenuation for Input Filter | Mhz | o.1 | 1 | 10 | 100 |  
          | ab | >20 | >40 | >40 | >20 |  
          |  |  |  
          | OUTPUT FILTERS | INPUT FILTERS |  
          | Drive | Filter Rating | Models | Drive | Filter Rating | Models |  
          | 5 Hp | 15 AMP | SAK-DRO-10 / 04 | 1 Hp | 5 AMP | SAK-DRV-5 / 04 |  
          | 7.5 Hp | 20  AMP | SAK-DRO-20 / 04 | 3 Hp | 10 AMP | SAK-DRV-10 / 04 |  
          | 15 Hp | 30 AMP | SAK-DRO-30 / 04 | 5 Hp | 15 AMP | SAK-DRV-15 / 04 |  
          | 25 Hp | 45  AMP | SAK-DRO-45 / 04 | 7.5 Hp | 20 AMP | SAK-DRV-20 / 04 |  
          | 30 Hp | 75 AMP | SAK-DRO-75 / 04 | 10 Hp | 30 AMP | SAK-DRV-30 / 04 |  
          |  | 20 Hp | 40 AMP | SAK-DRV-20 / 04*2# |  
          | 25 Hp | 60 AMP | SAK-DRV-30 / 04*2# |  
          | 30 Hp | 90 AMP | SAK-DRV-30 / 04*3# |  
          | 40 Hp | 120  AMP | SAK-DRV-30 / 04*4# |  | 
  
  
    |  |  |  | 
  
    |  |  | Power Line Filters for single phase AC Drives | 
  
    |  |  |  |  | 
  
    |  |  | 
      
        
          | Specification |  |  
          | Rated Voltage | 230V, 50HZ ( 440V,50Hz On request.) |  
          | Rated Current | 6A, 10A & 15A |  
          | Test Voltage | 1500v ac between Main terminals Shorted together & earth for 60 Secs. |  
          | Insulation Resistance | > 20 m ohm between mains terminals shorted together & earth at 500 VDC |  
          | Leakage Current | 2 * 0.2 mA max at 230V, 50Hz |  
          | Voltage Drop | 1 V rms Max |  
          | Operating Temperature Range | 55 c |  
          | Insertion Loss |  
          | Current Ratings AMPS |  | 3 | 6 | 10 |  |  
          | Common Mode Insertion Loss (dB in a 50 ohm system)
 FREQUENCY-MHz
 | 0.15 | >15 | >10 | >8 |  |  
          | 0.5 | >25 | >20 | >15 |  |  
          | 1.0 | >30 | >25 | >20 |  |  
          | 5.0 | >45 | >40 | >35 |  |  
          | 10 | >50 | >50 | >45 |  |  
          | 30 | >55 | >50 | >45 |  |  
          | Circuit Diagram |  |  
          |  |  |  | 
  
  
  
    |  |  |  |  |  |  |  | 
  
  
  
    | 
 |  |  |  |  |  | 
  
  
    
  
  